click for a better quality image |
 |
| Product |
Miniature Circuit Breakers (MCBs) |
| Standard |
CEI EN 60898 |
| N° poles |
1P |
1P+N |
2P |
3P |
3P+N |
4P |
| N° modules |
1 |
2 |
2 |
3 |
4 |
4 |
| Rated Voltage |
230/400V |
230V |
230V |
400V |
400V |
400V |
| Rated Current (A) |
0,5 - 4A |
6 - 63A |
0,5 - 4A |
6 - 63A |
0,5 - 4A |
6 - 63A |
0,5 - 4A |
6 - 63A |
0,5 - 4A |
6 - 63A |
6 - 63A |
| Tripping characteristic |
C/D |
B/C/D |
C/D |
B/C/D |
C/D |
B/C/D |
C/D |
B/C/D |
C/D |
B/C/D |
B/C/D |
| Rated breaking capacity |
20000 |
6000 / 10000 |
20000 |
6000 / 10000 |
20000 |
6000 10000 |
20000 |
6000 / 10000 |
20000 |
6000 / 10000 |
6000 / 10000 |
| Rated frequency (Hz) |
50/60 |
| Protection degree |
IP20 |
| Limitation Class |
3 (for In 32A, characteristic C/D, up to 10000A) |
| Maximum cross-section of connectable cable (flexible/rigid) |
25/35 mm² |
|
| |

click for a better quality image |
|
| Product |
Residual Current Circuit Breakers with overcurrent protection (RCBOs) |
| Standard |
CEI EN 61009-1 |
| N° poles |
1P+N |
2P |
3P+N |
3P+N |
| N° modules |
2 |
3 |
in just 4 DIN modules |
5 |
| Rated Voltage |
230V |
230V |
400V |
400V |
| Rated Current (A) |
6 - 50A |
6 - 50A |
6 - 32A |
40 - 63A |
| Tripping characteristic |
B/C/D |
B/C/D |
B/C/D |
B/C/D |
| Rated breaking capacity (A) |
6000 |
6000/10000 |
6000 |
6000 |
| Type |
AC/A |
AC/A |
AC/A |
AC/A |
| Sensitivity (mA) |
10/ 30/ 100/ 300/ 500 |
10/ 30/ 100/ 300/ 500 |
10/ 30/ 100/ 300/ 500 |
30/ 300/ 500 |
| Rated frequency (Hz) |
50/60 |
| Protection degree |
IP20 |
| Limitation Class |
3 (for In 32A, characteristic C/D, up to 10000A) |
| Maximum cross-section of connectable cable (flexible/rigid) |
25/35 mm² |
|
| |

click for a better quality image |
|
| Product |
Residual Current Circuit Breakers without overcurrent protection (RCCBs) |
| Standard |
CEI EN 61008-1 |
| N° polole |
2P |
4P |
| N° modules |
2 |
4 |
| Rated Voltage |
230V |
400V |
| Rated Current (A) |
16 - 80A |
16 - 63A |
| Rated conditional Short Circuit current (A) |
6000 (with gl fuse) |
| Type |
AC/A/AS |
AC/A/AS |
| Sensitivity (mA) |
10/30/300/500 |
10/30/300/500 |
| Rated frequency (Hz) |
50/60 |
| Protection degree |
IP20 |
| Maximum cross-section of connectable cable (flexible/rigid) |
25/35 mm² |
|